Location: Wailea, HI
Services
- Energy Management System(EMS)
- Occupancy based setbacks/recovery mode
- Deep mesh RF zigbee network
- Occupancy based lighting control
- Door lock integration (Ving/Assa abloy)
- Balcony door switches/transmitters
HVAC Controls
- When the room is not rented and is unoccupied the thermostat is in deep temperature set back recovery mode.
- When the room is rented and unoccupied the thermostat is set to a more comfortable setback but still in energy conservation mode.
- When the room is occupied the thermostat will bring and maintain the temperature to meet the guest desired setting.
- When the room is occupied but motion is not detected other processes such as heat signatures and nighttime override settings are implemented.
- When the room is in extended unoccupied state all connected lighting will turn off after a predetermined amount of time.
- Lighting control the occupancy detection system described above will provide occupancy status to lighting devices.
- When the room is no longer occupied, all connected lighting will turn off after a predetermined amount of time.
Design Notes
- The Smartcon system will include in-room temperature control via an income E7 thermostat.
- Occupancy controlled lighting via built-in occupancy sensor on the E7 thermostat.
- Door contact or door lock integration will monitor door activity and adjust occupancy state.